Jump to: navigation, search

Overview

This document describes GridLAB-D implementation of the CONSTANT_PQ mode inverter with droops. The implementation is based on the existing inverter CONSTANT_PQ mode source codes. In the original CONSTANT_PQ mode inverter, during event mode simulation, the inverter current outputs are computed based on the reference power values and the terminal voltage values; During delta mode simulation, the inverter real and reactive power outputs are compared with the reference values in each delta time step, and a PI controller is connected after the comparison, for the calculation of the updated current injection Iout from inverter.

caption


With the droop mode inverter implemented inside the CONSTANT_PQ mode inverter, the reference power values will be updated by checking the measured feeder frequency and the inverter terminal voltage with the droop curve setpoints.

caption
caption


The capability to run in delta mode is implemented in battery object. The battery can be attached to the droop inverter.

GridLAB-D implementation

PQ constant mode inverter with droop curves example

This inverter object is a CONSTANT_PQ mode inverter with droop curves. The inverter is implemented under the inverter type four_quadrant_control_mode. The CONSTANT_PQ mode is chosen by selecting four_quadrant_control_mode as CONSTANT_PQ. The droop curves are implemented only when dynamic_model_mode is selected as PI. The droops are by default not selected for the CONSTANT_PQ mode inverter, user has to set inverter_droop_fp as true for p/f droop, and set inverter_droop_vq as true for q/v droop. The delay time are by default the same as the delta time step defined, user can define the delay time with larger values.

In this example, the delay time of seeing the measured frequency and terminal voltage is set as 0.01 s. The droop of f/p curve is set as 0.000001, and the droop of v/q curve is set as 0.005.

module generators;
object inverter {
     parent 1370;
     name const_pq_inv1;
     inverter_type FOUR_QUADRANT;
     use_multipoint_efficiency FALSE;
     four_quadrant_control_mode CONSTANT_PQ;
     generator_status ONLINE;
     inverter_efficiency 0.99;
     rated_power 300 kVA;
     P_Out 200000;
     Q_Out 100000;
     V_In 1000+0j;
     I_In 1000+0j;
     flags DELTAMODE;
     dynamic_model_mode PI; 
     inverter_convergence_criterion 0.001;
     // PI controller parameters
     kpd 0.001;
     kid 0.09;
     kpq 0.001;
     kiq 0.09;
     // Droop curve parameters
     inverter_droop_fp true;
     Tfreq_delay 0.01;
     R_fp 0.000001;
     inverter_droop_vq false;
     Tvol_delay 0.01;
     R_vq 0.005;
}

Properties

This table lists the properties related to VSI implementation. Some parameters used by other types of inverters can be found in the inverter wiki page.

Property name Type Unit Description
inverter_type enumeration none Defines type of inverter technology and efficiency of the unit (FOUR_QUADRANT , PWM, TWELVE_PULSE, SIX_PULSE, TWO_PULSE).
Should choose FOUR_QUADRANT for VSI object.
four_quadrant_control_mode enumeration none Control mode of the inverter when FOUR_QUADRANT (NONE, CONSTANT_PQ, CONSTANT_PF, CONSTANT_V, VOLT_VAR, VOLTAGE_SOURCE).
Should choose VOLTAGE_SOURCE for VSI object.
use_multipoint_efficiency bool none A boolean flag to toggle using Sandia National Laboratory's multipoint efficiency model
generator_status enumeration none Defines if generator is in operation or not (ONLINE, OFFLINE)
inverter_efficiency double none four_quadrant_control_mode:The efficiency of the inverter
rated_power double VA four_quadrant_control_mode:The per phase rated power of the inverter
P_Out double VA Value to output in four quadrant control mode CONSTANT_PQ and VOLTAGE_SOURCE
Q_Out double VAr Value to output in four quadrant control mode CONSTANT_PQ and VOLTAGE_SOURCE
V_In complex V DC voltage passed in by the DC object (e.g. solar panel or battery)
I_In complex A DC current passed in by the DC object (e.g. solar panel or battery)
flags unit32 none Object flag to be used for indication of delta mode inclusion
dynamic_model_mode enumeration none DELTAMODE: Underlying model to use for deltamode control
inverter_convergence_criterion double none The maximum change in error threshold for exiting deltamode
kpd double none DELTAMODE: The d-axis proportional gain for the current modulation PI controller
kpq double none DELTAMODE: The q-axis proportional gain for the current modulation PI controller
kid double none DELTAMODE: The d-axis integration gain for the current modulation PI controller
kiq double none DELTAMODE: The q-axis integration gain for the current modulation PI controller
Parameters related to droop curve settings
inverter_droop_fp bool none DELTAMODE: Boolean used to indicate whether inverter f/p droop is included or not. False by default
Tfreq_delay double s DELTAMODE: The time constant for delayed frequency seen by the inverter. If not defined in glm file, it will be the same as the delta time step value
inverter_droop_vq bool none DELTAMODE: Boolean used to indicate whether inverter q/v droop is included or not. False by default
Tvol_delay double s DELTAMODE: The time constant for delayed voltage seen by the inverter. If not defined in glm file, it will be the same as the delta time step value
R_fp double none DELTAMODE: The droop parameter of the f/p droop.
R_vq double none DELTAMODE: The droop parameter of the v/q droop.


Test cases

In IEEE 123-bus feeder, one diesel generator of isochronous mode is placed at the swing bus, and one inverter of p/f droop and constant_Q mode is placed at node 54.
At 2001-08-01 12:00:10.001 PST, three-phase load 49 increases based on the given players. The diesel generator increases its power to maintain the feeder frequency. Although there is f/p droop enabled in the inverter, since no speed change is detected, inverter real power outputs are kept the same as the reference value after transient.

caption

To run this case, please find in the autotest in GridLAB-D generator module.

See Also