WECC CMPLDW test

I think it would be useful to have a third test, e.g., and reciprocating AC compressor load subjected to a 3-cycle voltage drop to 0.35 puV, followed by a slow delayed voltage recovery starting at 0.7 puV running up to 1.1 puV for about 20 seconds and then returning to 1.0 put in 10 seconds. This would allow us to validate the FIDVR behavior of motor type D in the WECC composite load model. Dchassin (talk) 16:26, 1 August 2016 (UTC)